EG-UPSO-1000 |
Q: | How to activate the ECO mode? Where is the ECO function? |
A: | You can set it via the Iservice Tool |
Q: | When I press the OFF button, the UPS just goes to the STANDBY mode and the fan continues spinning producing much noise. The manual states that there should be the SHUTDOWN mode. So, how to shut it down completely without disconnecting it from the mains? |
A: | It can only be switched to bypass or standby, and then the mains input is disconnected to completely shut down. |
Q: | Each button pressing produces a loud beep. How to turn that beeping off? |
A: | Disconnect the mains input and switch the machine to battery mode. Then press and hold the first and third keys in battery mode for more than 1 second |
Q: | Is it possible to make the UPS to shutdown when it has no load (so, when the only desktop connected to it is turned off)? |
A: | There is no such function for the time being |
- Online type UPS: double voltage conversion without switching the power
- USB control interface
- LCD display
- Short circuit protection
- Compatible with power generators of any brand
- Overload, surge, spike and lightning protection
- Audible and visual alarms
- Overcharge and overdischarge protection
Specifications |
UPS type: online, pure sine wave |
Input: 220V AC ± 25%, 50Hz / 60Hz ± 10% |
Output: 220V AC ± 1%, 50Hz / 60Hz ± 0.5% (on battery) |
Output power factor: > 0.99 |
Inverter output efficiency (resistive load): 85%, any load type is allowed |
Switching time: zero |
Backup time: 8...20 mins (depends on the load) |
Battery: 151 x 65 x 95 mm, sealed lead-acid 12 V / 9 Ah / 2.35 kg x 2 pcs, 24VDC |
Charge time: 90% capacity restored in 3 hours |
External battery connectors: yes |
Sockets: input IEC C14, outputs: 1x schuko sockets + 3x IEC sockets |
Interface communication: USB; optional slots: RS485 / dry contacts / SNMP |
Operating conditions: 0°C~40°C, at humidity 10~90%RH non condensing |
Noise: < 45 dB (at 1 meter distance) |
Power: 1000 VA (900 W) |
Dimensions: 144 x 312 x 216 mm |
Product weight: 11 kg |
"Cold-start" function
|
System requirements |
In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work.
|
Package contents |
UPS |
Power cord |
USB cable |
Software CD |
Spare fuse
|
Packing details |
Q'ty in crtn, pcs | 1 |
Crtn volume, CUM | 0.0320256 |
Crtn weight, kgs | 10.6 |
Individual package size LxWxH: | 400x240x320 mm |
Carton size LxWxH: | 417x240x320 mm |
Country of origin | CN |
Barcode | 8716309124836 |
Customs code | 8504408590 |
Packaging | brown carton box |
Trade Mark |
|